Power supply: 3-phase, 5-wire or 3-phase 4-wire 380VAC±10% 50/60HZ
Measuring temperature range: -49℃~119℃/-56℉~245.2℉
Temperature measurement accuracy: -20℃~50℃±1℃, other±1.5℃; -4℉~122℉±2℉, other ±3℉
Temperature control range: -49℃~119℃/-56℉~245.2℉
Temperature resolution: 0.1℃/1℉
Current measurement range: 2~80A
Current display resolution: 0.1A
Accuracy of current detection: ±2A (0~30A), ±5% (within the nominal range of other transformers)
Compressor delay: 0~10 minutes
Output capacity of relay contacts: 5A/240VAC
Maximum allowable continuous output current of compressor circuit: 14A (5HP)/21A (10HP)/28A (15hp)
Maximum allowable continuous output current of defrosting circuit: 14A (5HP)/21A (10HP)/28A (15hp)
Maximum allowable continuous output current of fan circuit: 7A (5~15HP)
Working environment: 0℃~40℃
Sensor type: NTC (10KΩ/25℃, B value 3435K)
Sensor wire length: 3 pcs sensors at 5m/8m (including probe length)
Dimension

Wiring Diagram